Return to the Clark Homepage
 
 

 

Plenum Rated Cat6A 10G UTP Cable

 

CN423C6AP

10G Ethernet Networking - designed for 10 Gb/s data networking

500 MHz Bandwidth - provides bandwidth for high data rate applications

ETL Verified to TIA-568-B.2-10 - verified to meet or exceed TIA standards for Cat6A cable

ETL Verified to ISO/IEC 11801 - verified to meet or exceed ISO/IEC standards for Cat6 cable

UL Plenum Rated CMP - UL and CSA rated for installation in most plenum environments

The CN423C6AP is an enhanced plenum rated Category 6A cable for 10 Gb/s networking and data applications. Constructed from four precision twisted pairs, the CN423C6AP is tested to meet or exceed TIA-568-B.2-10 and ISO/IEC 11801 specifications. UL rated plenum Type CMP and CSA FT-6, the CN423C6AP is suitable for installation in most plenum installation environments.

 

Materials & Dimentions

Conductors

(8) 23AWG Solid BC (configured as four pairs)

Insulation

FEP, .009" wall

Insulation Color Code

Pair 1: Blue & White w/ Blue Stripe

Pair 2: Orange & White w/ Orange Stripe

Pair 3: Green & White w/ Green Stripe

Pair 4: Brown & White w/ Brown Stripe

Separator Cross-Web
Jacket

Plenum PVC

Overall Diameter

.354"

 

Cross Sectional Diagram

 

Mechanical Characteristics

Operating Temperature Weight Agency Listing
-20degC to +80degC

59 lbs/Mft

ETL listed Type CMP

C(ETL) listed FT-6

 

Electrical Characteristics

DCR DCR Unbalance Characteristic Impedance Skew Capacitance
9.38 Ω/100m

5%

100 Ω (+/-15)

45 ms/100m

(max.)

330 pF/100m (pair-to-pair ground unblanced)

 

Frequency (MHz) 1 4 10 16 20 31.3 62.5 100 200 250 400 500
Insertion Loss
(max.)
2.1 3.8 5.9 7.5 8.4 10.5 15.0 19.1 27.6 31.1 40.1 45.3
Return Loss
(max.)
20.0 23.0 25.0 25.0 25.0 23.6 21.5 20.1 18.0 17.3 15.9 15.2
NEXT
(min.)
74.3 65.2 59.3 56.2 54.8 51.9 47.4 44.3 39.8 38.3 35.2 33.8
PS-NEXT
(min.)
72.3 63.3 57.3 54.2 52.8 49.9 45.4 42.3 37.8 36.3 33.2 31.8
ELFEXT
(min.)
67.8 55.8 47.8 43.7 41.8 37.9 31.9 27.8 21.8 19.8 15.8 13.8
PS-ELFEXT
(min.)
64.8 52.8 44.8 40.7 38.8 34.9 28.8

24.8

18.8 16.8 12.8 10.8
PS-ANEXT
(min.)
67.0 67.0 67.0 67.0 67.0 67.0 65.6 62.5 58.0 56.5 53.5 52.0
PS-AELFEXT
(min.)
67.0 66.2 56.2 54.1 52.2 48.3 42.3 38.2 32.2 30.2 26.2 24.2

All values listed in above table are dB/100m of cable.

 




 
 
2018 Clark Wire & Cable       1-800-CABLE-IT  (800-222-5348)